CIF Benefits from RCx

Campus Instructional Facility (CIF) has quickly become an on-campus hub, drawing tens of thousands of students per week through its doors. A wide array of classes are there, and public space areas are often populated as study areas. The building went up in 2021 and in these years since, F&S Retrocommissioning (RCx) experts figured it likely they would work on the building, with its high usage and advanced mechanical systems.

CIF was also introduced as a geothermal-powered facility, meaning it draws on the relative stability of below-earth temperatures to keep the building warm or cool, depending on need. Special windows prevent hot temperatures, and change colors. Panels in individual rooms keep users comfortable. The air handling unit has dual energy recovery wheels, rooms have CO2 and humidity sensors, and it was designed with good window and wall insulation and air sealing. The building was given a LEED® Platinum rating once built, one of just five on the Urbana campus.

But there’s always room for improvement, and RCx efforts have resulted in a 38%drop in energy use (kBtu/ft2/year). Here’s how.

Students on study area steps in Campus Instructional Facility (CIF)

RCx Prescriptions

Retrocommissioning teams make solutions happen – a team is deployed to the site with the express goal of, through hardware, software, education, and investigation, making the building more effective at heating and cooling its occupants. RCx has made improvements to more than 350 buildings totaling a cost avoidance of $160M since 2007. Occupancy is one piece of low-hanging fruit within reach of most any building’s energy use reduction plans. Ideally, you should use less energy when there’s fewer people in the building, like at night, during unscheduled days, holidays or break periods, and in summer months.

Bringing 40,000 students through each set of doors per week raises periodic peak needs — as they open the door to enter or exit, more conditioned air will need to offset that fresh air that just swept inside.

Andy Robinson, F&S engineer in energy services administration, was on the team addressing CIF concerns. The results, says Robinson, have made CIF a “contender for most efficient building on campus, especially one that has so many students in it.”

“We save a lot of energy in large campus rooms by turning down the airflow based on the CO2 demand or when nobody is there at all,” said Robinson. “Every room at CIF already had CO2 sensors, but the program wasn’t letting the air go as low as we determined it could. CIF is the busiest classroom building on campus, but there are still plenty of hours when rooms were sitting empty or with one person keeping it running too high.”

6 Solutions

A few improvements were made simply done thanks to metering findings done by Robinson and the RCx team.

  • For one, the primary air handling unit would run all through the night hours and early morning in times when the building is empty. This was solved with some adjustments made to in-room sensors.
  • Secondly, a chilled water valve, which is a backup to cool the building, would not close all the way. They spotted this hardware issue and worked with their team of dedicated F&S craftspersons – sheet metal workers, temperature control mechanics, and electricians are teamed with engineers and programmers to get on site and get it done.
  • Thirdly, classroom use in summer months have seen “very limited” use, and many are very large, so using the CO2 sensors is even more important.
  • Fourth, the radiant panels which keep comfortable temps in each room are fairly unique on campus, especially paired with a geothermal heat recovery chiller, and they required special programming. Areas like the radiant heated concrete monument steps are an ideal warm place on a cool day.
  • Fifth, some locations of plumbing show water chemistry issues, leading to valve failures in the heat recovery chiller. This has now been humming along well for the past year.
  • Sixth, the amount of campus-generated steam should go down based on preheat and reheat temperatures changing to a lower temperature. The building does a great job of keeping its heat in and needing very little cooling/steam needed from campus.

The project lasted March until June in 2024, and results have been impressive.

Electricity use is down 6% (in kWh), chilled water reduction of 72% and a steam reduction of 52%, with more expected this winter.

“For saving energy, reducing the room load and the 100% outdoor air is the first step,” said Robinson. “Last winter we were able to cut the campus steam to the air handler to essentially 0 by lowering the water temperature from 160 to 115F, which the geothermal HRC production on-site can produce. We can do this because the dual heat recovery wheels are so efficient at extracting the exhaust heat and preheating the outdoor air, and because the building is so well designed.”

Lessons learned from the design and construction of CIF have been incorporated into the Gies College of Business’ new Wymer Hall. This is the newest geothermal high efficiency classroom/office building, and it will be interesting to see how the two stack up in energy once the commissioning bugs are worked out.

Resources

Shop Spotlight: Sheetmetal Workers

You want real power? Try stepping (safely!) into an air handling unit (AHU) running full bore in the bowels of the Beckman Institute.

The 1.46 inches of static pressure within the AHU is strong enough to knock you over when stepping through the doorway – if you’re close enough, it’ll try to drag you in. The small room features one thing: a giant fan whirring at top speed.

There, air is pressurized, conditioned, and distributed to all five stories of offices, public spaces, classrooms, and high-tech laboratories. Four giant fans do the ‘supply’ and four more do ‘return’, all of them original to the building’s 1986 birth. And they are key to the comfort and success of building occupants, including researchers and students. Each fan replaces 100,000 cubic feet of air per minute.

“These fans are going 24/7, 365 days a year. They never stop,” said Guy Grant, sheetmetal worker. He noted that especially during hot summer months, all four fans are going simultaneously to keep the institute cool. Grant and colleagues Matt Althaus, Joe George, and Shaun Chesnut work as a team on this project and other work at Beckman.

Needless to say, these fans need to be repaired every two to five years. One new supply fan has already been installed, and another will be done before the fall semester. The final two supply fans are likely to be replaced each of the next two years.

Sheetmetal workers are working on the project alongside other trades, including electricians, pipefitters, and the temperature control shop.

Shop Spotlight: Temperature Control

It’s been a big couple of years for HVAC. Heating, ventilation, and air conditioning technologies have never been under more scrutiny and attention, due to the response to the COVID-19 pandemic.

A multi-disciplinary team, including leaders from F&S in construction, HVAC, and safety, oversaw the examination of all current and installation of new university HVAC systems. To see a published list of completed work, visit:
https://go.fs.illinois.edu/HVACSystems.

When time came to turn wrenches and make adjustments, the temperature control shop was there to help complete
the work. Temperature control oversees public spaces, offices, and classrooms, sure. And comfort for students, faculty, and staff is important. But often overlooked is the importance of HVAC in research laboratories: precise and reliable temperatures and humidity levels are needed to ensure scientific integrity. In other spaces, ventilation is essential to life safety needs for faculty and students.

Travis Huls, temperature control foreperson, saw factors like these in refurbishments and upgrades at Edward R. Madigan Laboratory.

“The recent temperature control upgrade there comes to mind, because our group coordinated with electricians and programmers to upgrade several large air handlers and heat exchangers,” said Huls. “Madigan is one of the largest lab and animal research facilities on campus, and doing an upgrade of that scope while keeping the equipment operational was a challenging task.”


Just as important to assessing and completing the work is updating customers as the project completes phases, according to Huls.


“It takes skilled technicians and good communication, our people are not only efficient at diagnosing and repairing HVAC controls, but are also very experienced in customer service. To be a good service provider you need people that have both of those skill sets, and our team is exceptional.”